Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Mail is now working! Feel free to request an account. Accounts are available to invested enthusiasts/technicians in the industry. :)

45 Greenbriar Drive NW, Calgary

From FireAlarmPedia
System Specifications
FACP: Edwards iO1000
FACP Location: East Prof. Office Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2023

45 Greenbriar Drive NW is the address of a small shopping/professional plaza in the Greenwich shopping district of Calgary, Alberta, Canada. The building contains the following tenants: Studio Esthetica, Citizen Salon Studios, Pelvic Floor Physio Calgary, Masala Bhavan Express, Holistic Institute of Health & Fertility, and Abbey’s Creations Greenwich. The building was built in 2023, and the fire alarm system is original.

System Specifications

FACP

The building is protected by an Edwards iO1000 addressable fire alarm system. The panel is located in the east professional office entrance vestibule. The system runs Edwards’ Signature addressable protocol, and the system coding is temporal.

Notification Appliances

All notification appliances are Edwards “Genesis” G1AVRF horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Edwards SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are Edwards SIGA-OSD addressable optical smoke detectors throughout the building, mounted on Edwards SIGA-SB bases.

Modules

There are Edwards SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Edwards SIGA-IM addressable isolator modules on the SLC.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.