| System Specifications |
|---|
| FACP: None System Type: 120V Hardwired System Line Voltage: 120VAC System Coding: Continuous Date of last known Upgrade: N/A <be /> Most Recent Known Modification: 2000s, Smoke Alarms Year Opened: 1968 |
722 5a St NW is the address of a small walkup apartment building in the Sunnyside neighborhood of Calgary, Alberta, Canada. The building was built in 1968, and the fire alarm system is original, with replacement parts installed as deficiencies occur.
System Specifications
The building is protected by a 120V hardwired fire alarm system, with bells and initiating devices wired in series. The system coding is continuous.
Notification Appliances
All notification appliances are Edwards "Adaptabel" 340 vibrating bells (6" gong).
Initiating Devices
Pull Stations
All pull stations but one are Edwards CCS-452 conventional single-action pull stations.
There is a Notifier NFM-950B conventional single-action pull station on the 1st floor as a deficiency replacement.
Automatic Detection Devices
There are American Sensors ESA5011 ionization smoke alarms with internal relays on each floor.
There are Potter CR-135W conventional 135°F fixed-temperature/rate-of-rise heat detectors in the laundry room and west storage room.
There are Edwards 245A conventional 135°F fixed-temperature heat detectors in the boiler room and east storage room.