System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2013

7745 66 St SE is the address of an industrial building in the Great Plains Industrial district of Calgary, Alberta, Canada. The building was built in 2013, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main electrical room. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

Most notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
The south unit's shop area has System Sensor "L-Series" P2RLA horn/strobes (red, wall-mount, bilingual lettering, set to 15cd).
For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount, set to 75cd) outside the main electrical room.

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors at the top the stairwell, in the main electrical room, and in the south data room.
There is a Notifier FST-851A addressable 135°F fixed-temperature heat detector in the main mechanical/sprinkler room.
All detectors but one are mounted on System Sensor B210LPA bases; the stairwell detector is mounted on a System Sensor B224BIA isolator base.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.