9595 Enterprise Way SE, Calgary, AB

From FireAlarmPedia
System Specifications
FACP: EST iO64
FACP Location: Main Entrance
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2012

9595 Enterprise Way SE is the address of a small industrial building in Calgary, Alberta, Canada. The building was built in 2012, and the fire alarm system is original.

System Specifications

FACP

The building is protected by an EST iO64 addressable fire alarm system. The panel is located at the main entrance. The system runs EST's Signature addressable protocol, and the system coding is temporal.

Notification Appliances

All indoor notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
For outdoor notification, there is an Edwards CS405-7A-T weatherproof remote strobe (red, 15/75cd) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors at the top of the main stairwell and in the main electrical room.
There is an Edwards SIGA-PD addressable photoelectric smoke detector at the top of the mezzanine stairs as a deficiency replacement.
There is an EST SIGA-HRS addressable 135-degree fixed-temperature/rate-of-rise heat detector in the sprinkler room.
All detectors are mounted on EST SIGA-SB bases.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There is an EST SIGA-CR addressable relay module for fan shutdown.
There are EST SIGA-IM addressable isolator modules on the SLC.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.