System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Bylaw Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2013 Year Opened: 1912, 2000s |
AHS EMS Station 3 is an emergency medical services station located at 1807 Macleod Trail SE, in Calgary, Alberta, Canada. The building is owned and maintained by The City of Calgary. The building was built in 1912 as Fire Station 2, and was renovated to house bylaw services and EMS in the 2000s. The fire alarm system was fully upgraded in 2013.
System Specifications (2013-present)
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the bylaw entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances
All indoor notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside the bylaw main entrance.
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors at the top of each stairwell, in all EMS storage rooms, and in the main electrical and IT rooms.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors throughout most areas.
There are Notifier FST-851A addressable 135°F fixed-temperature heat detectors in the EMS apparatus bay.
All aforementioned detectors are mounted on Notifier B710LPA bases.
There are System Sensor DNRA duct smoke detector housings equipped with Notifier FSP-851A addressable photoelectric heads on all air handling units.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.