| System Specifications |
|---|
| FACP: ADT EST3 FACP Location: Fire Equipment Room System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VDC (Visual) System Coding: Slow Whoop + Message Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2000s Year Opened: 1977 |
Arlington Cemetery Station is a WMATA train station located at 700 North West St, Alexandria, Virginia. The station was built in 1989, and the fire alarm system was upgraded in the 2000s.
System Specifications
FACP
The building is protected by an ADT EST3 addressable fire alarm system. The panel is likely located in the fire equipment room. The system runs ADT’s Signature addressable protocol, and is equipped with voice evacuation. The evacuation signal is slow whoop followed by the default EST message.
Annunciators
There is an ADT EST3-LCDANN annunciator in the station manager’s office.
Notification Appliances
Most areas have a mix of Edwards “Genesis” WG4WF-SVMC weatherproof speaker/strobes (white, set to 70V) and Edwards WG4RF-SVMC weatherproof speaker/strobes (red, set to 70V).
Areas requiring additional visual coverage have a mix of Edwards WG4WF-S weatherproof remote speakers (white, set to 70V) and Edwards WG4RF-S weatherproof remote speakers (red, set to 70V).
The platform area has Edwards CS405-7A-T weatherproof remote strobes (red, wall-mount, 15/75cd).
Some areas have HyperSpike TCPA-10 high-output speakers.
Initiating Devices
Pull Stations
All pull stations are ADT ADT-278 addressable dual-action pull stations.
Automatic Detection Devices
There are ADT ADT-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in the elevator lobbies, mounted on EST SIGA-SB bases.