| System Specifications |
|---|
| FACP: Mircom FX-2000 FACP Location: 2nd Floor Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Mircom Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2016 |
Auburn Landing is an apartment complex owned and operated by Boardwalk. This page will cover Building 20, located at 20 Auburn Bay Street SE, in Calgary, Alberta, Canada. The building was built in 2016, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the 2nd floor electrical room. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.
This panel is interconnected to the system in Building 30 via relay and monitor modules.
Annunciators
There is a Mircom RAX-LCD annunciator paired with a Mircom RAX-1048TZDS annunciator in the main entrance vestibule.
Both annunciators are mounted in a Mircom BB-1002 enclosure.
Booster Panels
There is a Mircom BPS-1100 11-amp booster power supply in the main floor electrical room.
Notification Appliances
Most common area notification appliances are Mircom "Select-A-Horn/Strobe" FHS-340R horn/strobes (red, wall-mount, set to electromechanical/15cd).
Some areas have Mircom FHS-340W horn/strobes (white, wall-mount, set to electromechanical/15cd).
All suite bedrooms have Mircom MH-S25WA silenceable mini-horns (white).
Initiating Devices
Pull Stations
All pull stations are Mircom MS-401AD addressable single-action pull stations.
Automatic Detection Devices
There are Mircom MIX-2251BA addressable photoelectric smoke detectors in all corridors, at the top of each stairwell, at the top of the elevator shaft, in all electrical and storage rooms, and in some mechanical rooms.
There are Mircom MIX-5251RAPA addressable 135°F fixed-temperature/rate-of-rise heat detectors in some mechanical rooms.
Most detectors are mounted on System Sensor B210LPA bases; detectors at fire separations are mounted on System Sensor B224BIA-WH isolator bases.
There is a System Sensor "InnovAir Flex" DNRA duct smoke detector housing equipped with a Mircom MIX-2251APA addressable photoelectric head on the main air handling unit.
Modules
There are Mircom MIX-M500MA addressable monitor modules monitoring signals from Building 30, and supervising the sprinkler system's tamper, flow and low air switches.
There are Mircom MIX-M500RA addressable relay modules sending signals to Building 30.
There are System Sensor M500XA isolator modules on both SLCs.
EOLs
There are Mircom MP-300 end of line resistor plates on all sprinkler and Class-B signal circuits.