Avenida Village Building B

From FireAlarmPedia
System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2021
Year Opened: 1988

Avenida Village is an open-air shopping centre in Calgary, Alberta, Canada. This page will cover Building B, located at 12100 Macleod Trail. The building was built in 1988, and was renovated to house a farmer’s market in 2020. The fire alarm system was fully upgraded in 2021.

System Specifications

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main electrical room, on the east side of the building. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Power Supplies

There is a Notifier ACPS-610 10-amp booster power supply located next to the main FACP.

Notification Appliances

All indoor notification appliances are System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, bilingual lettering).
For outdoor notification, there is a System Sensor “SpectrAlert Advance” SRKA weatherproof remote strobe (red, wall-mount) outside the main electrical room.

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FST-851A addressable 135°F fixed-temperature heat detectors in the mechanical and electrical rooms, mounted on System Sensor B210LPA bases.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.