| System Specifications |
|---|
| FACP: Notifier NFS2-3030C FACP Location: Parkade Main Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2016-2017 |
Axess at Currie Barracks is a condo/townhome complex located at 95 Burma Star Road SW, in Calgary, Alberta, Canada. The complex consists of three buildings: 1000 and 3000 are condos, and 2000 are townhomes. The building was built in 2016 and 2017, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the main electrical room in the parkade. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Annunciators
There are Notifier LCD-160 annunciators paired with Notifier ACM-24AT annunciators in the main lobbies of 1000 and 3000, and in the elevator lobby of 2000.
Booster Panels
There are Notifier FCPS-24S8C 8-amp booster power supplies in all electrical rooms in 3000, some electrical rooms in 1000, some areas in the parkade, and in the snow melt room.
Notification Appliances
All common area notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
All suite bedrooms have System Sensor MHWZA silenceable mini-horns (white).
For outdoor notification, there are System Sensor SRKA weatherproof remote strobes (red, wall-mount) outside each building's main entrance and outside some townhomes.
There are System Sensor SCRKA weatherproof remote strobes (red, ceiling-mount) outside the entrance of most townhomes.
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout all corridors, at the top of each stairwell and elevator shaft, and in each elevator lobby.
There is a Notifier FSP-951A addressable photoelectric smoke detector in 1000 as a deficiency replacement.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There are System Sensor "Innovair Flex" DNRA duct smoke detector housings equipped with Notifier FSP-851A addressable photoelectric heads on all make-up air units.
Modules
There are Notifier FDM-1A addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FMM-1A addressable monitor modules supervising some tamper switches.
There are Notifier FRM-1A addressable relay modules for elevator recall and MUA shutdown.
There are Notifier ISO-XA isolator modules on all three SLCs.
There are System Sensor AIM-1A suite isolation modules isolating each suite's signals.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.