BOW45

From FireAlarmPedia
System Specifications
FACP: Notifier NFS2-640C
FACP Location: South Entrance
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2021

BOW45 is a 3-story medical building located at 4620 Bow Trail SW, Calgary, Alberta. The building was built in 2021, and the fire alarm system is original.

System Specifications (2021-present)

FACP

The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located at the south entrance. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

All indoor notification appliances are from System Sensor’s “L-Series” line of products.
Most areas have System Sensor P2RLA horn/strobes (red, wall-mount, set to 15cd).
Areas requiring additional visual coverage have System Sensor SRLA remote strobes (red, wall-mount, set to 15cd).
One retail unit has System Sensor PC2WLA horn/strobes (white, ceiling-mount, set to 15cd).
One floor has System Sensor PC2RLA horn/strobes (red, ceiling-mount, set to 15cd).
One washroom has a System Sensor SWLA remote strobe (white, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor “SpectrAlert Advance” P2RKA weatherproof horn/strobe (red, wall-mount) on the third floor patio, and a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside the south entrance.

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-951A addressable photoelectric smoke detectors in each elevator lobby, stairwell and throughout unit 220.
The kitchen and laundry rooms of 220 have Notifier FST-951RA addressable thermal fixed-temperature/rate-of-rise heat detectors.
All detectors are mounted on System Sensor B300A-6 bases.
There is a System Sensor DNRA duct smoke detector housing on the third floor air handling unit, fitted with a Notifier FSP-951A addressable photoelectric smoke detector head. It is wired to a System Sensor RA100ZA indicator.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules for AHU shutdown and elevator recall.
There are Notifier ISO-XA isolator modules on each SLC.

EOLs

There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.