| System Specifications |
|---|
| FACP: Edwards EST3 FACP Location: Unknown System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (alert) Temporal (alarm) Strobes Synchronized: Yes, Genesis Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2010 |
Banff Mineral Springs Hospital is a hospital located at 305 Lynx St, Banff, Alberta. The facility is operated by Covenant Health. The hospital was built in 2010, and the fire alarm system is original.
System Specifications (2010-present)
FACP
The building is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, followed by the alarm signal, temporal.
Annunciators
There is an Edwards EST3-6ANN annunciator in the main entrance vestibule, fitted with the LCDXL1 display.
Notification Appliances
All notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage pull stations.
Automatic Detection Devices
There are EST SIGA-IPHS addressable combo ionization/photoelectric smoke/135°F fixed-temperature heat detectors throughout the building, mounted on SIGA-SB bases.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM isolator modules on the SLC.
Each NAC has an EST “SignalMaster” G1M signal control module to allow 4-wire operation for two-stage.
EOLs
There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.