| System Specifications |
|---|
| FACP: Notifier AFP-200 FACP Location: Main Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: 1990s Most Recent Known Modification: 2010s, Smokes Year Opened: 1963 |
The Banff Visitor Centre is a visitor centre located at 224 Banff Avenue, in Banff, Alberta, Canada. The building was built in 1963, and the fire alarm system was upgraded in the mid-1990s.
System Specifications (1990s-present)
FACP
The building is protected by a Notifier AFP-200 addressable fire alarm system. The panel is located at the main entrance. The system runs Notifier's CLIP addressable protocol, and the system coding is continuous.
Notification Appliances
All notification appliances are System Sensor "Multi-Alert" MASS24MA sounder/strobes (red, wall-mount, set to 500Hz?).
Initiating Devices
Pull Stations
All pull stations are Notifier NFM-950B conventional single-action pull stations, wired to Notifier MMX-101A addressable monitor modules.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors at the top of each stairwell, mounted on System Sensor B210LPA bases.
EOLs
There are Notifier EOL-CR end of line resistor plates on all signal circuits.