| System Specifications |
|---|
| FACP: Mircom FX-2000 FACP Location: Main Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: No Date of last known Upgrade: 2014 Most Recent Known Modification: N/A Year Opened: 1978 |
The Bertha Gold Jewish Seniors Residence is an independent senior living facility located at 1603 90 Ave SW, in Calgary, Alberta, Canada. The building was built in 1978, and the fire alarm system was upgraded in 2014.
System Specifications (2014-present)
FACP
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main electrical room, in the basement. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.
Annunciators
There is a Mircom RAX-LCD annunciator paired with a Mircom RAX-1048TZDS annunciator in the main entrance vestibule. Both annunciators are mounted in a Mircom BB-1002 enclosure.
Notification Appliances
All notification appliances are Mircom "Select-A-Horn/Strobe" FHS-340R horn/strobes (red, wall-mount, set to electromechanical/15cd).
Notification appliances are located throughout the corridors; there are no insuite devices in this building.
Initiating Devices
Pull Stations
All pull stations are Mircom MS-401AD addressable single-action pull stations.
Automatic Detection Devices
There are Mircom MIX-2251APA addressable photoelectric smoke detectors throughout all aboveground corridors, at the top of each stairwell, in the 5th floor duct shaft, and in the elevator lobbies of all aboveground floors.
There are Mircom MIX-5251RAPA addressable 135°F fixed-temperature/rate-of-rise heat detectors in all basement rooms, in the basement elevator lobby, in the main floor utility room, in all laundry rooms, and in all garbage rooms on floors 2-5.
There are Mircom MIX-5251APA addressable 135°F fixed-temperature heat detectors in the main floor garbage room, and in the main floor storage room.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There is a System Sensor "Innovair Flex" DNRA duct smoke detector housing equipped with a Mircom MIX-2251APA addressable photoelectric head on the main air handling unit.
Modules
There are Mircom MIX-M500MAPA addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Mircom MIX-M500RAPA addressable relay modules serving various purposes.
There are System Sensor M500XA isolator modules on the SLC.
EOLs
There are Mircom MP-300 end of line resistor plates on all signal circuits; sprinkler EOLs are located in the devices.