Boston Pizza (Dalhousie)

From FireAlarmPedia
System Specifications
FACP: Mircom FA-106
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: N/A
Most Recent Known Modification: 2020s, FACP
Year Opened: 1996


Boston Pizza is Canada’s largest chain of casual dining restaurants. This particular restaurant is located at 5005 Dalhousie Dr NW #703, in Calgary, Alberta, Canada. The building was built in 1996, and the fire alarm system is mostly original.


System Specifications

Please note that this system only supervises Boston Pizza.

FACP

The restaurant is protected by a Mircom FA-106 conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is temporal.
This panel replaced a Notifier SFP-400B in the early 2020s.


Notification Appliances

The dining and lounge areas have Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock LSP-24-VFR strobe plates (15cd).
The kitchen has a Mircom BL-6A motor bell (6” gong), and the second floor hall has a Simplex 2901-9723 motor bell (6” gong); both are mounted on Wheelock RSSP-24MCW-FR strobe plates (red, set to 15cd).


Initiating Devices

Pull Stations

All pull stations but one are Notifier MPS-950B conventional single-action pull stations.
There is a Mircom MS-401 conventional single-action pull station in the kitchen as a deficiency replacement.


Automatic Detection Devices

There are two Mircom TD-135 conventional 135°F fixed-temperature heat detectors in the kitchen.
There are Edwards 245A conventional 135°F fixed-temperature heat detectors in the second floor storage and electrical rooms.
There is an FDD CR-135 conventional 135°F fixed-temperature/rate-of-rise heat detector in the kitchen server area.
There is a System Sensor C2W-BA conventional photoelectric smoke detector at the top of the stairwell.
The kitchen suppression system is connected to the fire alarm system.


EOLs

There are Notifier EOL-CR end of line resistor plates on all circuits.