System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2009

Brewsters is a brewing company and chain of restaurants with locations across Alberta. This particular restaurant is located at 11 McKenzie Towne Ave SE, in Calgary, Alberta, Canada. The building was built in 2009, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

All indoor notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
The rooftop patio has System Sensor P2RKA weatherproof horn/strobes (red, wall-mount).
There is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors at the top of each stairwell, in all elevator lobbies, at the top of the elevator shaft, and in the second floor lobby area.
There are Notifier FST-851HA addressable 190°F fixed-temperature heat detectors throughout the kitchen.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in all kitchen storage rooms and in the garbage room.
All detectors are mounted on Notifier B710LPA bases.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the kitchen suppression system, and the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules for fan shutdown.

EOLs

There are Notifier EOL-CR end of line resistor plates on the kitchen suppression system circuit, and on all sprinkler and signal circuits.