CNRL Jackfish Lodge

From FireAlarmPedia
System Specifications
FACP: Notifier NFS2-640C
FACP Location: Utility Room
System Type: Two-Stage Networked Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Most Recent Known Modification: 2025, FACP
Year Opened: 2013

Canadian Natural Resources Ltd is an oil and gas production company. This page will cover the Jackfish Lodge, a workers' camp located near Conklin, Alberta, Canada. The camp was built in 2013, and the fire alarm systems are original.
Please note that the system is a Notifier NOTI-FIRE-NET network, and was constructed all as one building.

System Specifications (Main Lodge)

FACP

The main lodge is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located in the utility room. The system runs Notifier's FlashScan addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, and the alarm signal is temporal.

Annunciators

There is a Notifier NCA-2C annunciator paired with a custom graphic in the main entrance vestibule.

Boosters

There is a Notifier ACPS610 10-amp booster power supply beside the main FACP.

Notification Appliances

Most notification appliances are System Sensor "SpectrAlert Advance" P4RA horn/strobes (red, wall-mount, set to 15cd).
There are System Sensor PC4WA horn/strobes (white, ceiling-mount, set to 30cd) in some areas.
Each washroom has a System Sensor SRA remote strobe (red, wall-mount, set to 15cd).
For exterior notification, there is a System Sensor SRKA weatherproof remote strobe (red, set to 75cd) outside.

Initiating Devices

Pull Stations

All pull stations are Notifier N-MPS-2A addressable two-stage pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors in most areas.
There are Notifier FST-851A addressable 135°F fixed-temperature heat detectors in areas such as janitor rooms.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There are System Sensor "Innovair Flex" DNRA duct smoke detector housings equipped with Notifier FSP-851A addressable photoelectric heads on all air handling units.


Modules

There are Notifier FDM-1A addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on all SLCs.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.


System Specifications (Dorms)

System Specifications
FACP: Notifier NFS-320C
FACP Location: Dorm Entrances
System Type: Single-Stage Networked Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Most Recent Known Modification: 2022 (Boosters & Sounder Bases)
Year Opened: 2013

FACP

The dorms are protected by Notifier NFS-320C addressable fire alarm systems. The panels are located at the entrance of each building. The systems run Notifier's FlashScan addressable protocol, and the system coding is temporal for all systems.

Annunciators=

There are Notifier LCD2-80 annunciators paired with Notifier ACM-24AT annunciators at the exit of each dorm.

Booster Panels

There are Notifier PSE-6C 6-amp booster power supplies below each panel.

Notification Appliances

All notification appliances are System Sensor "SpectrAlert Advance" PC2WA horn/strobes (white, ceiling-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSI-851A addressable ionization smoke detectors throughout all common areas in E, F, G, H and K.
There are Notifier FSP-851A addressable photoelectric smoke detectors in each dorm room, as well as hallways in A, C and D.
The hallways of B & J have Notifier FSP-951A addressable photoelectric smoke detectors.
All common area detectors are mounted on System Sensor B210LPA bases, while all dorm room detectors are mounted on System Sensor B200SRA sounder bases.

Modules

There are Notifier FDM-1A addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on all SLCs.

EOLs

There are a mix of Notifier EOL-CR, Edwards EOL-P1 and Mircom MP-300 end of line resistor plates on all sprinkler and signal circuits.