CPKC Ogden Building 4 (1881 Lodge)

From FireAlarmPedia
System Specifications
FACP: Simplex 4010ES
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 29VDC
System Coding: Temporal
Strobes Synchronized: Yes, IDNAC
Date of last known Upgrade: 2010s
Most Recent Known Modification: N/A
Year Opened: 1914

CPKC is a railway headquartered in Calgary, Alberta. This page will cover Building 4 of the Ogden Campus, also known as the 1881 Lodge. The building is the main hotel for CPKC employees, and is located at 7550 Ogden Dale Road SE, in Calgary, Alberta, Canada. The building was built in 1914, and was extensively renovated in the 2010s. The fire alarm system was upgraded as part of the 2010s renovation.

System Specifications (2010s-present)

FACP

The building is protected by a Simplex 4010ES addressable fire alarm system. The panel is located in the main electrical room. The system runs Simplex's IDNet addressable initiating and IDNAC addressable indicating protocols, and the system coding is temporal.

Annunciators

There is a Simplex 4606-9102 annunciator paired with a Simplex 4602-9101 annunciator at the main entrance.

Booster Panels

There is a Simplex 4009 IDNAC repeater below the main FACP.

Notification Appliances

All indoor notification appliances are Simplex "TrueAlert ES" 49AV-WWF addressable horn/strobes (white, wall-mount, set to 15cd via FACP).
For outdoor notification, there is a Simplex 49VO-WRFO-C addressable weatherproof remote strobe (red, wall-mount) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations are Simplex 4099-9004 addressable single-action pull stations.

Automatic Detection Devices

There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors in all guest rooms, throughout all corridors, in all housekeeping rooms, throughout the lobby, and in all electrical, data and mechanical rooms.
There are Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors in all janitor and food prep closets.
All guest room detectors are mounted on Simplex 4098-9794 isolator bases, while all other detectors are mounted on Simplex 4098-9792 bases.

Modules

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules for AHU shutdown.
There are Simplex 4090-9116 isolator modules on the SLC.

EOLs

There are Simplex 2081-9040C end of line resistor plates on all sprinkler circuits.