Calgary Christian Elementary School

From FireAlarmPedia
System Specifications
FACP: Notifier AFP-200
FACP Location: South Stairwell
System Type: Single-Stage Hybrid-Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: 2004
Most Recent Known Modification: N/A
Year Opened: 1963, 1974, 1978, 1993

Calgary Christian Elementary School is a Christian elementary school located at 5029 26 Ave SW, in Calgary, Alberta, Canada. The building was built in 1963, was expanded in 1974 and 1978, and had portable classrooms added in 1993. The fire alarm system was upgraded in 2004.

System Specifications (2004-present)

FACP

The building is protected by a Notifier AFP-200 hybrid-addressable fire alarm system. The panel is located in the south stairwell. The system runs Notifier's CLIP addressable protocol, and the system coding is temporal.

Notification Appliances

Most notification appliances are System Sensor "SpectrAlert" P1224MCA horn/strobes (red, wall-mount, set to 15cd).
Some areas have System Sensor S1224MCA remote strobes (red, wall-mount, set to 15cd).
All portables have Notifier KMS-6-24A motor bells (6" gong).

Initiating Devices

Pull Stations

All pull stations are Notifier MPS-950B conventional single-action pull stations.
These are wired to Notifier FMM-101A addressable monitor modules in the main building.

Automatic Detection Devices

There are Notifier FSI-851A addressable ionization smoke detectors in the main office and at the top of each stairwell.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in all locker, storage and mechanical rooms.
All aforementioned detectors are mounted on Notifier B710LPA bases.
There are FDD CR-135 conventional 135°F fixed-temperature/rate-of-rise heat detectors in all portables.
There is a Notifier FSD-751PLA addressable photoelectric duct smoke detector on the air handling unit.

Modules

There is a Notifier FMM-1A addressable monitor module supervising the kitchen suppression system.

EOLs

There are Notifier EOL-CR end of line resistor plates on all conventional and signal circuits.