System Specifications |
---|
FACP: Simplex 4007ES FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, SmartSync Date of last known Upgrade: N/A Year Opened: 2017 |
The Calgary Fire Department is the fire department serving The City of Calgary. This page will cover Station 7, located at 2708 4 Street NW, in Calgary, Alberta, Canada. The station was built in 2017, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Simplex 4007ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.
Notification Appliances
All indoor notification appliances are Simplex “TrueAlert” 4906-9127 horn/strobes (red, wall-mount, set to 15cd).
For outdoor notification, there is a Simplex 4906-9105 weatherproof remote strobe (red, wall-mount) outside the main entrance.
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
Automatic Detection Devices
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 bases.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising the kitchen suppression system, and the sprinkler system’s tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on the SLC.
EOLs
There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits, and on the kitchen suppression system.