More actions
System Specifications |
---|
FACP: Simplex 4100U FACP Location: Automotive Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal? Strobes Synchronized: Yes, EST Self-Sync Date of last known Upgrade: 2000s Year Opened: 1999 |
Canadian Tire is a Canadian chain of department stores. This particular store is located at 11839 Kingsway NW, in Edmonton, Alberta, Canada. The store was built in 1999, and the fire alarm system was upgraded in the 2000s; the notification appliances remain original.
System Specifications (2000s-present)
FACP
The building is protected by a Simplex 4100U addressable fire alarm system. The panel is located in the automotive entrance vestibule. The system runs Simplex's IDNet addressable protocol, and the system coding is likely temporal.
Notification Appliances
All notification appliances are General Signal MB10-24 motor bells (10" gong) mounted on Edwards 403-5A-R strobe plates (15cd).
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9001 addressable single-action pull stations.
Automatic Detection Devices
There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors at the top of each stairwell, mounted on Simplex 4098-9792 bases.
There are Simplex 4098-9755 addressable duct smoke detector housings with Simplex 4098-9714 photoelectric heads on all air handling units.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
EOLs
There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.
Former System Specifications (1999-2000s)
Former System Specifications |
---|
FACP: Edwards EST2 FACP Location: Automotive Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous? Strobes Synchronized: Yes, EST Self-Sync Date of last known Upgrade: N/A Year Installed: 1999 Year Decommissioned: 2000s |
FACP
The building was protected by an Edwards EST2 addressable fire alarm system. The panel was located in the automotive entrance vestibule. The system ran Edwards' Signature addressable protocol, and the system coding was likely continuous.
Notification Appliances
All notification appliances were General Signal MB10-24 motor bells (10" gong) mounted on Edwards 403-5A-R strobe plates (15cd).
These are still in use on the Simplex system.
Initiating Devices
Pull Stations
All pull stations were EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There were EST SIGA-PS addressable photoelectric smoke detectors at the top of each stairwell, mounted on EST SIGA-SB bases.
There were EST SIGA-DH duct smoke detector housings with EST SIGA-PS addressable photoelectric heads on all air handling units.
Modules
There were EST SIGA-WTM addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There were EST SIGA-CR addressable relay modules serving various purposes.
EOLs
There were Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.