| System Specifications |
|---|
| FACP: EST QuickStart QS1 FACP Location: Main Lobby Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR (FACP) 24VDC (booster) |
The Carriage House Inn is a large hotel located at 9030 Macleod Trail South, in Calgary, Alberta, Canada. The hotel was built in 1970, and the fire alarm system was upgraded in 2008.
System Specifications (2008-present)
FACP
The hotel is protected by an EST QuickStart QS1 addressable fire alarm system. The panel is located to the right of the main lobby entrance. The system runs EST’s Signature addressable protocol, and the system coding is temporal.
Booster Panels
There is an Edwards BPS6A booster power supply below the main FACP.
Notification Appliances
All notification appliances are EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors in all guest room corridors and stairwells, mounted on EST SIGA-SB bases.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on the SLC.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.