| System Specifications |
|---|
| FACP: Simplex 4100ES FACP Location: Various System Type: Two-Stage Networked Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 29VDC (Visual) System Coding: Unknown Strobes Synchronized: Yes, IDNAC Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2019 |
Cavendish Farms Centre is a recreation centre located at 74 Mauretania Road W, in Lethbridge, Alberta, Canada. The building was built in 2019, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Simplex 4120 networked fire alarm system. All nodes are Simplex 4100ES addressable fire alarm panels; Nodes 1-3 are located in the YMCA entrance vestibule, and Node 4 is located in the arena entrance vestibule. The system runs Simplex's IDNet addressable initiating and IDNAC addressable indicating protocols, is equipped with voice evacuation, and is configured for two-stage operation. The messages and/or tones are unknown at this time.
Notification Appliances
Most notification appliances are Simplex "TrueAlert ES" 49SV-APPLW addressable speaker/strobes equipped with 49SVC-WRFIRE covers (red, wall-mount, set to 15cd).
All lobbies, corridors and common areas have Simplex 49SO-APPLC addressable remote speakers equipped with 49SOC-CRFIRE covers (red, ceiling-mount).
All areas with remote speakers have Simplex 49VO-WRF addressable remote strobes (red, wall-mount, set to 15cd); these can also be found in areas such as washrooms.
For outdoor notification, there is a Simplex 49VO-WRFO-C weatherproof addressable remote strobe (red) outside the YMCA entrance.
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004CA addressable two-stage single-action pull stations.
Automatic Detection Devices
There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors in some areas.
There are Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
All aforementioned detectors are mounted on Simplex 4098-9792 bases.
There are Simplex 4098-9755 duct smoke detector housings equipped with Simplex 4098-9714 addressable photoelectric heads on all air handling units.
Firefighter's Telephones
There are Simplex 2084-9107-C fire phones at all code-required locations.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising all kitchen suppression systems, the generator's run/trouble contacts, the fire pump's run/trouble contacts, and the sprinkler system's tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on all SLCs.
EOLs
There are Simplex 2081-9040C end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.