| System Specifications |
|---|
| FACP: EST FireShield FACP Location: West Entrance System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Self-Sync Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2005 |
The Church of Jesus Christ of Latter Day Saints is a church with locations around the world. This particular church is located at 81 Royal Elm Drive NW, in Calgary, Alberta, Canada. The building was built in 2005, and the fire alarm system is original.
System Specifications
Please note that this information is accurate to 2023.
FACP
The building is protected by an EST FireShield FS1004G conventional fire alarm system. The panel is located at the west entrance. The system coding is temporal.
Notification Appliances
Most notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
All washrooms have Edwards G1RF-VM remote strobes (red, wall-mount, FIRE marking, set to 15cd).
For outdoor notification, there is an Edwards CS405-7A-T weatherproof remote strobe (red) outside the main entrance.
Initiating Devices
Pull Stations
All pull stations are Edwards 278B-1120 conventional dual-action pull stations.
Automatic Detection Devices
There are Edwards EC30U-3 conventional photoelectric smoke detectors throughout all corridors.
There are System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors in some rooms.
There are Edwards 284B-PL conventional 194°F fixed-temperature heat detectors in the sprinkler and electrical rooms, in some closets, and throughout the attic.
EOLs