Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Mail is now working! Feel free to request an account. Accounts are available to invested enthusiasts/technicians in the industry. :)

Churchill Station (Valley Line)

From FireAlarmPedia
System Specifications
FACP: Notifier NFS-320C
FACP Location: Unknown
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2023

Churchill Station is a light rail train station in Edmonton, Alberta, Canada. This page will cover the Valley Line building, which serves as a connector between the Valley Line and Metro/Capital Line platforms. The building was built in 2023, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel location is unknown. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Annunciators

There is a Notifier LCD2-80 annunciator paired with two Notifier ACM-24AT annunciators in the main lobby.

Notification Appliances

Most notification appliances are System Sensor “L-Series” P2RLA-E horn/strobes (red, wall-mount, set to 15cd).
Some areas have System Sensor PC2RLA-E horn/strobes (red, ceiling-mount, set to 15cd).
There are a System Sensor SRLA-E remote strobes (red, wall-mount, set to 15cd) in the Metro/Capital Line building above the doors to this building.

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-951A addressable photoelectric smoke detectors throughout the building, mounted on System Sensor B300A-6 bases.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Notifier EOL-CR end of line resistor plates on all signal circuits.

Accessories

There is a TOA RM-200SF emergency paging microphone next to the annunciator; this microphone is connected to the building’s public address system.