| System Specifications |
|---|
| FACP: Notifier NFS-320C FACP Location: Main Mechanical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Most Recent Known Modification: 2026, LED Strobe Year Opened: 2017 |
Days Inn & Suites is a chain of budget hotels owned by Wyndham. This particular hotel is located at 292243 Wagon Wheel Blvd, in Balzac, Alberta, Canada. The building was built in 2017, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main mechanical room. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Annunciators
There is a Notifier LCD2-80 annunciator paired with a Notifier ACM-24AT annunciator in the main entrance vestibule.
Booster Panels
There are Notifier ACPS-610 addressable 6-amp booster power supplies in the storage rooms on floors 2-4.
Notification Appliances
Most common area notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
Some common areas have System Sensor SRA remote strobes (red, wall-mount, set to 15cd).
Most guest rooms have System Sensor MHWZA silenceable mini-horns (white) paired with System Sensor SWA remote strobes (white, wall-mount, set to 15cd).
Some guest rooms have System Sensor MHW1A mini-horns (white).
Some guest rooms have System Sensor "L-Series" SWLA remote strobes (white, wall-mount, bilingual lettering, set to 15cd) as deficiency replacements.
One guest room has a System Sensor SRLED-B remote strobe (red, wall-mount, bilingual lettering, set to 15cd) as a deficiency replacement.
Initiating Devices
Pull Stations
All pull stations are Notifier N-MPS-SA addressable single-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout all corridors, at the top of each stairwell, in the lobby, in the breakfast room, in the guest laundry and 3rd floor staff laundry rooms, and in the meeting room.
Some areas have Notifier FSP-951A and FSP-951A-IV addressable photoelectric smoke detectors as deficiency replacements.
There are Notifier FST-851A addressable 135°F fixed-temperature heat detectors in the main laundry room, in the storage rooms on floors 2-4, in the mechanical room, in the kitchen, and at the top of the elevator shaft.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There is a System Sensor "Innovair Flex" DNRA duct smoke detector housing equipped with a Notifier FSP-951RA addressable photoelectric head on the makeup air unit in the 4th floor staff room.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and Class-B signal circuits.