Duffield School

From FireAlarmPedia
System Specifications
FACP: Notifier NFS2-640C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2025
Most Recent Known Modification: N/A
Year Opened: 1954, 1963, 1988, 2005

Duffield School is a K-9 school located at 1 Main Street, in Duffield, Alberta, Canada. The school is part of the Parkland School Division. The school was built in 1954, and was expanded in 1963, 1988 and 2005. The fire alarm system was upgraded in 2004, and was fully replaced in 2025. This page will showcase both the current and 2004 systems.

System Specifications (2025-present)

FACP

The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

All indoor notification appliances are System Sensor "L-Series" P2RLED-B horn/strobes (red, wall-mount, bilingual lettering, set to 15cd).
For outdoor notification, there is a System Sensor "SpectrAlert Advance" P2RKA weatherproof horn/strobe (red, wall-mount) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-951A addressable photoelectric smoke detectors in some areas.
There are Notifier FST-951A addressable 135°F fixed-temperature heat detectors in most areas, and throughout the crawlspace.
All aforementioned detectors are mounted on System Sensor B300A-6 bases.
There are System Sensor "Innovair Flex" DNRA duct smoke detector housings equipped with Notifier FSP-951A addressable photoelectric heads on all air handling units.

Modules

There are Notifier FRM-1A addressable relay modules serving various purposes.

EOLs

There are Notifier EOL-CR end of line resistor plates on all signal circuits.

Former System Specifications (2004-2025)

Former System Specifications
FACP: Simplex 4007ES
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: No
Most Recent Known Modification: 2020s, FACP
Year Installed: 2004
Year + Reason Decommissioned: 2025, Simplex

FACP

The building was protected by a Simplex 4007ES addressable fire alarm system. The panel was located in the main entrance vestibule. The system ran Simplex's IDNet addressable protocol, and the system coding was temporal.
This panel replaced a Simplex 4010.

Notification Appliances

All indoor notification appliances were System Sensor "SpectrAlert" P1224MCA horn/strobes (red, wall-mount, set to 15cd).
For outdoor notification, there was a System Sensor P1224MCKA weatherproof horn/strobe (red, wall-mount) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations were Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices

There were Simplex "TrueAlarm" 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors throughout the building.
There were Simplex 4098-9714 addressable photoelectric smoke detectors in some areas.
All aforementioned detectors were mounted on Simplex 4098-9792 bases.
There were Simplex 4098-9755 addressable photoelectric duct smoke detectors on all air handling units.

Modules

There were Simplex 4090-9002 addressable relay modules serving various purposes.

EOLs

There were Simplex 2081-9040C end of line resistor plates on all signal circuits.