| FACP: Notifier NFS2-640C FACP Location: Arena 2 Main Lobby System Type: Single-Stage Hybrid-Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 1980s, 2021 |
Eagle Builders Centre is a recreation complex located at 5302 Broadway Ave, in Blackfalds, Alberta, Canada. The complex consists of two arenas and a library; Arena 2 was built in the 1980s, and Arena 1 and the library were built in 2021. Arena 1 is home to the Blackfalds Bulldogs of the British Columbia Hockey League (BCHL). The fire alarm system was upgraded and installed in 2021.
System Specifications (2021-present)
FACP
The building is protected by a Notifier NFS2-640C hybrid-addressable fire alarm system. The panel is located in the main lobby of Arena 2. The system runs Notifier's FlashScan addressable protocol, and utilizes several Notifier XP6-MAA zone cards to accommodate conventional devices. The system coding is temporal.
Notification Appliances
Most notification appliances are System Sensor "L-Series" P2RLA-E horn/strobes (red, wall-mount, English lettering, set to 15cd).
Arena 1 has System Sensor PC2RLA-E horn/strobes (red, ceiling-mount, English lettering, set to 15cd) for additional coverage.
Some areas have System Sensor SRLA-E remote strobes (red, wall-mount, English lettering, set to 15cd).
Initiating Devices
Pull Stations
All pull stations in Arena 1 are Notifier NBG-12LX addressable dual-action pull stations.
All pull stations in Arena 2 are Notifier MPS-950B conventional single-action pull stations.
Automatic Detection Devices
There are Notifier FSP-951A addressable photoelectric smoke detectors at the top of each stairwell and at each end of the club level in Arena 1, mounted on System Sensor B300A-6 bases.
There are Chemtronics 601 conventional 135°F fixed-temperature/rate-of-rise heat detectors in each washroom in Arena 2.
There are heat detectors in each change room in Arena 2, likely FDD CR-135.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches in Arena 1, as well as the kitchen suppression system.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on all SLCs.
EOLs
There are Notifier EOL-CR end of line resistor plates on all conventional, sprinkler and signal circuits.