System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Year Opened: 2008 |
Earls is a Canadian chain of upscale dining restaurants. This particular restaurant is located at 1505 99 Street NW, in Edmonton, Alberta, Canada. The restaurant was built in 2008, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel location is unknown. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Annunciators
There is a Notifier ACM-24AT annunciator in the main lobby.
Notification Appliances
All notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
Automatic Detection Devices
None noticed.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the kitchen suppression system, and the sprinkler system’s tamper and flow switches.
EOLs
There are Notifier EOL-CW end of line resistor plates on all sprinkler and signal circuits.