Ecole Chavigny

From FireAlarmPedia
System Specifications
FACP: Edwards iO1000
FACP Location: CACF Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR (FACP)
24VDC (Boosters)
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: 2018
Most Recent Known Modification: N/A
Year Opened: 1973

Ecole Chavigny is a school located at 447 Rue Chavigny, in Trois-Rivieres, Quebec, Canada. The school was built in 1973, and the fire alarm system was upgraded in 2018.

System Specifications (2018-present)

FACP

The building is protected by an Edwards iO1000 addressable fire alarm system. The panel is located in the CACF room. The system runs Edwards' Signature addressable protocol, and the system coding is temporal.

Booster Panels

There are Edwards BPS10A 10-amp booster power supplies on the system.

Notification Appliances

Most notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Some areas have Edwards G1-HDVM horn/strobes (white, wall-mount, no marking, set to 15cd).
There are Edwards G1-HD remote horns (white, wall-mount, no marking) throughout the school for additional audible coverage.
There are Edwards G1AVRN horn/strobes (red, wall-mount, no marking, set to 15cd) as deficiency replacements.

Initiating Devices

Pull Stations

All pull stations are EST SIGC-270F addressable single-action pull stations.

Automatic Detection Devices

There are Edwards SIGA-PD addressable photoelectric smoke detectors throughout most areas.
There are Edwards SIGA-PHD addressable photoelectric smoke/135°F fixed-temperature heat detectors in some areas.
There are Edwards SIGA-HRD addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
All aforementioned detectors are mounted on EST SIGA-SB bases.
There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on all air handling units.

Modules

There are EST SIGA-CT1 and SIGA-CT2 addressable monitor modules supervising the generator's run/trouble contacts, and the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-CC1 addressable control modules triggering all power supplies.
There are EST SIGA-IM addressable isolator modules on the SLC.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all circuits supervised by monitor modules, and all signal circuits.