System Specifications
FACP: Simplex 4010ES
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 29VDC
System Coding: Temporal
Strobes Synchronized: Yes, IDNAC
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2016

Edgeway Townhomes is a townhome complex located at 11703 51 Ave NW, in Edmonton, Alberta, Canada. The building was built in 2016, and the fire alarm system is original.

System Specifications

Please note that this system only supervises the parkade and parkade stairwells.

FACP

The building is protected by a Simplex 4010ES addressable fire alarm system. The panel is located in the main electrical/fire panel room. The system runs Simplex's IDNet addressable initiating and IDNAC addressable indicating protocols, and the system coding is temporal.

Annunciators

There is a Simplex 4602-9102 annunciator outside.

Notification Appliances

All indoor notification appliances are Simplex "TrueAlert ES" 49AV-WRF addressable horn/strobes (red, wall-mount, set to various candelas).
For outdoor notification, there is a Simplex 49VO-WRFO-C addressable weatherproof remote strobe (red, wall-mount) outside by the annunciator.

Initiating Devices

Pull Stations

All pull stations are Simplex 4099-9004 addressable single-action pull stations.

Automatic Detection Devices

There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors at the top of each stairwell, and in all electrical and communications rooms, mounted on Simplex 4098-9792 bases.
There are Potter CF-200W conventional 200°F fixed-temperature heat detectors in all boiler and MUA rooms, wired to Simplex 4090-9001 addressable monitor modules.

Modules

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There is one Simplex 4090-9002 addressable relay module for MUA shutdown.
There are Simplex 4090-9116 addressable isolator modules on the SLC.

EOLs

There are Simplex 2081-9040C end of line resistor plates on all sprinkler circuits.