System Specifications |
---|
FACP: Simplex 4100ES FACP Location: Electrical Rooms System Type: Single-Stage Networked Addressable System Line Voltage: 120VAC NAC Voltage: 29VDC System Coding: Temporal Strobes Synchronized: Yes, IDNAC Date of last known Upgrade: N/A Year Opened: 2016 |
The Edmonton Brewery District is a shopping centre located at 12060 104 Ave NW, in Edmonton, Alberta, Canada. The centre consists of several buildings, all protected by one fire alarm system. The buildings were built in 2016, and the fire alarm system is original.
System Specifications
FACP
The centre is protected by a Simplex 4120 networked fire alarm system. The network consists of 2 Simplex 4100ES addressable fire alarm panels, located in underground electrical rooms. The system runs Simplex's IDNet addressable initiating and IDNAC addressable signaling protocols, and the system coding is temporal.
Notification Appliances
All indoor notification appliances are Simplex "TrueAlert ES" 49AV-WRF addressable horn/strobes (red, wall-mount, FACP-controlled to 15cd).
For outdoor notification, there is a Simplex 49VO-WRFO addressable weatherproof remote strobe (red, wall-mount) outside each building.
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
Automatic Detection Devices
There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors at the top of each stairwell.
There are Simplex 4098-9734 addressable 190°F fixed-temperature/rate-of-rise heat detectors in some kitchens and boiler rooms.
There are Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors in some mechanical and storage rooms.
All detectors are mounted on Simplex 4098-9792 bases.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising all kitchen suppression systems, and the sprinkler system's tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on all SLCs.
EOLs
There are Simplex 2081-9040C end of line resistor plates on all kitchen suppression and sprinkler circuits.