Financial Building/100 House

From FireAlarmPedia
System Specifications
FACP: Simplex 4100ES
FACP Location: CACF Room
System Type: Single-Stage Hybrid-Addressable
System Line Voltage: 120VAC
NAC Voltage: 70VRMS (audible)
24VDC (visual)
System Coding: Unknown
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: 2019
Year Opened: 1957

The Financial Building is a multi-use building located at 10621 100 Ave NW, Edmonton, AB. The building consists of offices and tenants on most floors, and the upper six floors have been converted to apartments. The building was completed in 1957, and the conversions took place in 2019. The fire alarm system was upgraded in 2019.

System Specifications (2019-present)

FACP

The building is protected by a Simplex 4100ES hybrid-addressable fire alarm system. The panel is located in the CACF room. The system runs Simplex's IDNet addressable protocol, and is equipped with voice-evacuation. The tones and/or messages are unknown at this time.

Annunciators

There is a Simplex 4100 Operator Interface in the main entrance vestibule.

Notification Appliances

All notification appliances are Simplex "TrueAlert" 4906-9153 speaker/strobes (white, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

Most pull stations are Edwards 270-SPO conventional single-action pull stations.
There are Simplex 4099-9004 addressable single-action pull stations in some areas.

Automatic Detection Devices

There are Simplex "TrueAlert" 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 bases.
There are Simplex 4098-9755 addressable photoelectric duct smoke detectors on all air handling units.

Modules

There are Simplex 4090-9001 addressable monitor modules supervising the fire pump, as well as the sprinkler system's tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 isolator modules on the SLC.

EOLs

There are Simplex 2081-9018C end-of-line resistor plates on all sprinkler, conventional and signal circuits.