G.H. Dawe Community Centre

From FireAlarmPedia
System Specifications
FACP: Edwards EST3
FACP Location: Unknown
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: 2023
Most Recent Known Modification: N/A
Year Opened: 1982

The G.H. Dawe Community Centre is a recreation centre located at 6175 67 St, in Red Deer, Alberta, Canada. The building was built in 1982, and was renovated in 2023. The fire alarm system was upgraded as part of the 2023 renovation.

System Specifications (2023-present)

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs Edwards' Signature addressable protocol, and the system coding is temporal.

Annunciators

There are Edwards EST3-LCDANN annunciators equipped with LCDXL1 displays in each entrance vestibule.

Notification Appliances

Most notification appliances are Edwards "Genesis" G1AVRF horn/strobes (red, wall-mount, FIRE marking, set to 15cd).
Some areas have Edwards G1VRF remote strobes (red, wall-mount, FIRE marking, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are Edwards SIGA-OSD addressable optical smoke detectors in some areas, mounted on EST SIGA-SB bases.
There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on all air handling units.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.

EOLs