More actions
System Specifications |
---|
FACP: Edwards EST3 FACP Location: By Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2008 Year Opened: 1991 |
Gregg Distributors is an industrial equipment supplier. This particular warehouse is located at 16215 118 Ave NW, Edmonton, AB, and is the largest location. The building was originally built in 1991, and was expanded in 2004 and 2008. The fire alarm system was upgraded in 2004.
System Specifications (2004-present)
FACP
The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located past the main entrance. The system runs Edwards’ Signature addressable protocol, and the system coding is temporal.
Booster Panels
There is likely an Edwards BPS6A 6-amp booster power supply on the system.
Notification Appliances
All notification appliances are Edwards “Genesis” G1-HDVM horn/strobes (white, wall-mount, no marking, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors in some parts of the building.
Other areas have EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.
All detectors are mounted on EST SIGA-SB bases.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
EOLs
There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.