FACP: Mircom FX-2000
FACP Location: Unknown
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2010

Hampton Inn & Suites is a chain of hotels owned by Hilton. The chain is headquartered in McLean, Virginia, USA, and has locations worldwide. This particular hotel is located at 128 Leva Ave, in Red Deer, Alberta, Canada. The building was built in 2010, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel location is unknown. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.

Annunciators

There is a Mircom RAX-LCD annunciator in the main entrance vestibule.

Booster Panels

There are likely three Mircom BPS-1100 11-amp booster power supplies on the system.

Notification Appliances

All common areas have Mircom "Select-A-Horn/Strobe" FHS-240R horn/strobes (red, wall-mount, set to 15cd).
All guest rooms have Mircom MH-S25WA silenceable mini-horns (white).
Handicap guest rooms have Mircom "Select-A-Strobe" FS-240W remote strobes (white, wall-mount, set to 15cd) in addition to the aforementioned mini-horns.

Initiating Devices

Pull Stations

All pull stations are Mircom MS-401AD addressable single-action pull stations.

Automatic Detection Devices

There are Mircom MIX-2251BA addressable photoelectric smoke detectors throughout all corridors, at the top of each stairwell, in each elevator lobby, and likely at the top of each elevator shaft.
There are Mircom MIX-5251RBA addressable 135°F fixed-temperature/rate-of-rise heat detectors in all mechanical rooms, and at one end of the pool area.
There is a Mircom MIX-2251TMBA addressable photoelectric smoke/135°F fixed-temperature heat detector at one end of the pool area.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There are likely Mircom "Innovair" MIX-DH200PLA addressable photoelectric duct smoke detectors on all air handling units.

Modules

There are Mircom MIX-M500DMA addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches.
There are Mircom MIX-M500MA addressable monitor modules supervising all boosters.
There are Mircom MIX-M500RA addressable relay modules serving various purposes, including stairwell pressurization.
There are System Sensor M500XA isolator modules on the SLC.

EOLs

There are Mircom MP-300 end of line resistor plates on all sprinkler and Class-B signal circuits.