| System Specifications |
|---|
| FACP: Mircom FX-2000 FACP Location: Main Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR (FACP) 24VDC (booster) System Coding: Temporal Strobes Synchronized: No Date of last known Upgrade: N/A Most Recent Known Modification: 2023 Year Opened: 2006 |
Hardy Sales is a perishable food distributor in Western Canada. This particular warehouse is located at 10559 46 St SE, Calgary, Alberta. The building opened in 2006, and was expanded in 2023. The fire alarm system is original.
System Specifications (2006-present)
FACP
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located at the main entrance. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.
There is a Potter PFC-4410 conventional releasing panel supervising the pre-action system.
Booster Panels
There is a Mircom INX-10A addressable 10-amp booster power supply on the mezzanine.
Notification Appliances
Most notification appliances are Mircom "Select-a-Horn/Strobe" FHS-240R horn/strobes (red, wall-mount, set to 15cd).
The freezer and chillers have System Sensor "SpectrAlert" P1224MCKA weatherproof horn/strobes (red, wall-mount, set to 75cd).
The new freezer has System Sensor "SpectrAlert Advance" PC2RKA weatherproof horn/strobes (red, ceiling-mount, set to 75cd).
Initiating Devices
Pull Stations
Most pull stations are Mircom MS-401AD addressable single-action pull stations.
The new freezer has Mircom MS-401 conventional single-action pull stations wired to Mircom MIX-M500MAPA addressable monitor modules.
Automatic Detection Devices
There is a Mircom MIX-2251BA addressable photoelectric smoke detector at the top of the stairs.
There are Protectowire linear heat detection systems in the freezers and coolers.
Modules
There is a Mircom IM-10 10-input addressable monitor module supervising the sprinkler system's tamper and flow switches, plus the main pre-action system.
There is a Mircom MIX-M500MAPA addressable monitor module supervising the new pre-action system.
EOLs
There are Mircom MP-300 end-of-line resistor plates on all sprinkler, pre-action and signal circuits.
System Specifications (New Pre-Action)
| System Specifications |
|---|
| FACP: Notifier NFS-320C FACP Location: Mezzanine Pre-Action Room System Type: Addressable System Line Voltage: 120VAC Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2023 |
FACP
The new expansion is protected by a Notifier NFS-320C addressable pre-action fire suppression system. The panel is located in the mezzanine pre-action room. The system runs Notifier's FlashScan addressable protocol.
Initiating Devices
Automatic Detection Devices
There is a Protectowire linear heat detection system in the freezer, see below for module information.
Modules
There is a Notifier FMM-1A addressable monitor module supervising Protectowire alarm.
There is a Notifier FDM-1A addressable dual-input monitor module supervising the Protectowire faults.
There is a Notifier FRM-1A addressable relay module for solenoid release.
EOLs
There are Notifier EOL-CR end-of-line resistor plates on all circuits.