Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Mail is now working! Feel free to request an account. Accounts are available to invested enthusiasts/technicians in the industry. :)

Hardy Sales Calgary

From FireAlarmPedia
System Specifications
FACP: Mircom FX-2000
FACP Location: Main Entrance
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR (FACP)
24VDC (booster)
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: N/A
Most Recent Known Modification: 2023
Year Opened: 2006

Hardy Sales is a perishable food distributor in Western Canada. This particular warehouse is located at 10559 46 St SE, Calgary, Alberta. The building opened in 2006, and was expanded in 2023. The fire alarm system is original.

System Specifications (2006-present)

FACP

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located at the main entrance. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.
There is a Potter PFC-4410 conventional releasing panel supervising the pre-action system.

Booster Panels

There is a Mircom INX-10A addressable 10-amp booster power supply on the mezzanine.

Notification Appliances

Most notification appliances are Mircom "Select-a-Horn/Strobe" FHS-240R horn/strobes (red, wall-mount, set to 15cd).
The freezer and chillers have System Sensor "SpectrAlert" P1224MCKA weatherproof horn/strobes (red, wall-mount, set to 75cd).
The new freezer has System Sensor "SpectrAlert Advance" PC2RKA weatherproof horn/strobes (red, ceiling-mount, set to 75cd).

Initiating Devices

Pull Stations

Most pull stations are Mircom MS-401AD addressable single-action pull stations.
The new freezer has Mircom MS-401 conventional single-action pull stations wired to Mircom MIX-M500MAPA addressable monitor modules.

Automatic Detection Devices

There is a Mircom MIX-2251BA addressable photoelectric smoke detector at the top of the stairs.
There are Protectowire linear heat detection systems in the freezers and coolers.

Modules

There is a Mircom IM-10 10-input addressable monitor module supervising the sprinkler system's tamper and flow switches, plus the main pre-action system.
There is a Mircom MIX-M500MAPA addressable monitor module supervising the new pre-action system.

EOLs

There are Mircom MP-300 end-of-line resistor plates on all sprinkler, pre-action and signal circuits.

System Specifications (New Pre-Action)

System Specifications
FACP: Notifier NFS-320C
FACP Location: Mezzanine Pre-Action Room
System Type: Addressable
System Line Voltage: 120VAC

Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2023

FACP

The new expansion is protected by a Notifier NFS-320C addressable pre-action fire suppression system. The panel is located in the mezzanine pre-action room. The system runs Notifier's FlashScan addressable protocol.

Initiating Devices

Automatic Detection Devices

There is a Protectowire linear heat detection system in the freezer, see below for module information.

Modules

There is a Notifier FMM-1A addressable monitor module supervising Protectowire alarm.
There is a Notifier FDM-1A addressable dual-input monitor module supervising the Protectowire faults.
There is a Notifier FRM-1A addressable relay module for solenoid release.

EOLs

There are Notifier EOL-CR end-of-line resistor plates on all circuits.