Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Mail is now working! Feel free to request an account. Accounts are available to invested enthusiasts/technicians in the industry. :)

Harvey's/Swiss Chalet (Shepard)

From FireAlarmPedia
System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2006

Harvey's/Swiss Chalet is a combination restaurant chain. Harvey's is a fast food-style burger restaurant chain and Swiss Chalet is a casual dining chain specializing in rotisserie chicken. This particular pair of restaurants is located at 4916 130 Ave SE, in Calgary, Alberta, Canada. The building was built in 2006, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

Most notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
The women's washroom likely has a System Sensor SRA remote strobe (red, wall-mount, set to 15cd).
The men's washroom has a System Sensor "L-Series" SRLA remote strobe (red, wall-mount, bilingual lettering, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.

Automatic Detection Devices

There are Notifier FST-851HA addressable 190°F fixed-temperature heat detectors throughout the kitchen.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
All detectors are mounted on Notifier B710LPA bases.

Modules

There is a Notifier FMM-1A addressable monitor module supervising the kitchen suppression system.

EOLs

There are Notifier EOL-CR end of line resistor plates on all kitchen suppression and signal circuits.