More actions
System Specifications |
---|
FACP: EST QuickStart QS4 FACP Location: Unknown System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: 20BPM (Alert) Temporal (Alarm) Strobes Synchronized: Yes, EST Self-Sync Date of last known Upgrade: N/A Year Opened: 2003, 2017 |
Heritage Park is a community centre located at 5100 41 Avenue, in Stony Plain, Alberta, Canada. The centre has two community halls and a pavilion. The building was built in 2003, and expanded in 2017. The fire alarm system is original.
System Specifications[edit | edit source]
FACP[edit | edit source]
The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel location is unknown. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the alarm coding is temporal.
Annunciators[edit | edit source]
There is an EST QSA-1-S annunciator in the main entrance vestibule.
Notification Appliances[edit | edit source]
All indoor notification appliances are Edwards “Genesis” G1-HDVM horn/strobes (white, wall-mount, no marking, set to 15cd).
For outdoor notification, there are Edwards “Integrity” 757-7A-T weather-rated horn/strobes (red, wall-mount, 15/75cd) outside the main entrance and mechanical room, and on the patio.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are EST SIGA-PS addressable photoelectric smoke detectors in some areas, mounted on EST SIGA-SB bases.
There are EST SIGA-DH duct detector housings with SIGA-PS heads on all air handling units.
Modules[edit | edit source]
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
EOLs[edit | edit source]
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.