| System Specifications |
|---|
| FACP: Vigilant VS2 FACP Location: Main Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR (FACP) 24VDC (Booster) System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2015 Year Opened: 1973 |
Hotel Blackfoot is a hotel located at 5940 Blackfoot Trail SE, in Calgary, Alberta, Canada. The hotel was built in 1973, and the fire alarm system was upgraded in 2015. Several system modifications and expansions have occurred in the 2020s.
System Specifications (2015-present)
System specifications have been confirmed as of 9/17/2026.
FACP
The building is protected by a Vigilant VS2 addressable fire alarm system. The panel is located in the main electrical room. The system runs Vigilant's GSA addressable protocol, and the system coding is temporal.
Annunciators
There is a Vigilant RLCD annunciator paired with a Vigilant RLED24 annunciator behind the front desk.
Both annunciators are mounted in a Vigilant RA-ENC2 enclosure.
Booster Panels
There is an Edwards BPS10AC 10-amp booster power supply beside the main FACP.
Notification Appliances
All notification appliances are Edwards “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Initiating Devices
Pull Stations
Most pull stations are Vigilant GSA-M270 addressable single-action pull stations.
The 6th floor stairwells have newly installed Kidde GSA-M270 addressable single-action pull stations.
Automatic Detection Devices
There are Vigilant V-PS addressable photoelectric smoke detectors in all hotel corridors, at the top of each stairwell, and at the top of the north elevator shaft.
There are Vigilant V-HRD addressable 135°F fixed-temperature/rate-of-rise heat detectors in all non-public rooms.
All aforementioned detectors are mounted on Vigilant B4U bases.
There are Kidde KI-OSD addressable photoelectric smoke detectors in the pool maintenance rooms and at the top of the west elevator shaft, mounted on Kidde KI-SB bases.
There are Vigilant GSA-SD addressable photoelectric duct smoke detectors on all air handling units.
Modules
There are Vigilant GSA-CT1 addressable monitor modules supervising the kitchen suppression systems, and the sprinkler system’s tamper and flow switches.
There are Vigilant GSA-CR addressable relay modules serving various purposes.
There are Vigilant GSA-IM addressable isolator modules on both SLCs.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.