| System Specifications |
|---|
| FACP: Notifier NFS-320C FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Most Recent Known Modification: 2021, FACP & Heat Year Opened: 2021 |
Intelcom is a shipping service specializing in small deliveries. This page will cover the Edmonton office, located at 4175 95 St NW, in Edmonton, Alberta, Canada. The building was built in 2005, and the fire alarm system is mostly original.
System Specifications
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
This panel replaced a Notifier AFP-200 in 2021.
Notification Appliances
Most notification appliances are System Sensor “SpectrAlert” P1224MCA horn/strobes (red, wall-mount, set to 15cd).
The office area and electrical room have System Sensor “L-Series” P2RLA-E horn/strobes (red, wall-mount, English lettering, set to 15cd) as deficiency replacements.
All accessible washrooms have System Sensor SRLA-E remote strobes (red, wall-mount, English lettering, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
The southeast warehouse exit pull station is a deficiency replacement.
Automatic Detection Devices
There are Notifier “Innovair” FSD-751RPLA addressable photoelectric duct smoke detectors on the air handling units (2 detectors total).
There is a Notifier FST-951A addressable 135°F fixed-temperature heat detector in the electrical room, mounted on a System Sensor B300A-6 base.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the fire pump’s run/trouble contacts, and the sprinkler system’s tamper and flow switches.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.