| System Specifications |
|---|
| FACP: Notifier NFS-320C FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2013 Most Recent Known Modification: N/A Year Opened: 2012 |
Iron Mountain is a North American company specializing in document destruction. This particular warehouse is located at 12828 184 St NW, in Edmonton, Alberta, Canada. The building was built in 2012, and the fire alarm system was installed in 2013.
System Specifications (2013-present)
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Booster Panels
There is a Notifier PSE-6C 6-amp booster power supply on the east wall.
Notification Appliances
All base building notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
There is one Notifier KMS-10-24A motor bell (10" gong) mounted on a Wheelock RSSP-24MCW-FR strobe plate (red, set to 15cd), which only activates in a VESDA Action event.
Initiating Devices
Pull Stations
Most pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
Some areas have Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors in some areas with low ceilings, mounted on System Sensor B210LPA bases.
There are several VESDA aspirating smoke detection systems in this building.
Modules
There are Notifier FDM-1A addressable dual-input monitor modules supervising the generator's run/trouble contacts, the fire pump's run/trouble contacts, and the sprinkler system's tamper and flow switches.
There is a Notifier XP10-MA 10-zone interface card supervising all VESDAs.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler, VESDA and signal circuits.