| System Specifications |
|---|
| FACP: Honeywell XLS140-2 FACP Location: North Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2008 Year Opened: 1985 |
Lakeland College is a post-secondary institution located in Vermilion, Alberta, Canada. This page will cover the Trades Centre. The building was built in 1985, and the fire alarm system was upgraded in 2008.
System Specifications (2008-present)
FACP
The building is protected by a Honeywell XLS140-2 addressable fire alarm system. The panel is located at the north entrance. The system runs Honeywell's FlashScan addressable protocol, and the system coding is temporal.
This panel is part of the Lakeland College campus-wide XLS-NET network.
Notification Appliances
All notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Honeywell XLS-MPS addressable dual-action pull stations.
Automatic Detection Devices
There are Honeywell TC806B1076CDN addressable photoelectric smoke detectors throughout most areas.
There are Honeywell TC806B1084CDN addressable photoelectric smoke/135°F fixed-temperature heat detectors in all electrical rooms and at all fire doors.
There are Honeywell TC808B1058CDN addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
There are Honeywell TC808B1066CDN addressable 190°F fixed-temperature heat detectors in the mechanical room.
All detectors are mounted on Notifier B710LPA bases.
Modules
There are Honeywell XLS-MM-AA addressable monitor modules supervising the sprinkler system's tamper and flow switches
There are Honeywell XLS-CM-RA addressable relay modules serving various purposes.
EOLs
There are Honeywell EOL-CR end of line resistor plates on all sprinkler and signal circuits.