Lakeland Mall

From FireAlarmPedia
System Specifications
FACP: Kidde VS4
FACP Location: West Entrance Vestibule
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous?
Strobes Synchronized: N/A
Date of last known Upgrade: 2010s
Year Opened: 1982

Lakeland Mall is a shopping mall located at 4420 Railway Avenue, in Vermilion, Alberta, Canada. The mall was built in 1982, and the fire alarm system was partially upgraded in the 2010s.

System Specifications (2010s-present)

FACP

The building is protected by a Kidde VS4 conventional fire alarm system. The panel is located in the west entrance vestibule. The panel is equipped with two Kidde RZI16-2 zone cards to accommodate the conventional devices. The system coding is likely continuous.
This panel replaced an Edwards Custom 6500 around 2021.

Annunciators

There is a Kidde K-RLCD-C annunciator paired with a Kidde K-RLED24 annunciator in the main entrance vestibule.
Both annunciators are mounted in a Kidde RA-ENC2 enclosure.

Notification Appliances

Most notification appliances are Edwards "Durabel" 6100D vibrating bells (10" gong).
There are Edwards 439D-10AWC vibrating bells (10" gong) in the rear hallway and part of Dollarama as deficiency replacement.
There are Fire-Lite/Notifier MB-G10-24 motor bells (10" gong) in MainStreet Hardware, installed in 1998.
There is an Edwards MB10-24 motor bell (10" gong) in AG Foods as a deficiency replacement.

Initiating Devices

Pull Stations

Most pull stations are Edwards 274-111 conventional single-action pull stations.
Some areas have Edwards 270-SPO conventional single-action pull stations.
There is a Notifier NFM-950B conventional single-action pull station at the MainStreet Hardware garden exit as a deficiency replacement.

Automatic Detection Devices

There is a System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detector in the mechanical room.
There is an Edwards EC30U-3 conventional photoelectric smoke detector in the electrical room.
There is an Edwards SD-2W conventional photoelectric duct smoke detector on the main rooftop unit.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all circuits.