| System Specifications |
|---|
| FACP: Notifier NFS2-3030C FACP Location: Parkade Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2018 Most Recent Known Modification: 2020s, Smoke Year Opened: 1980 |
Le Marchand Tower is an apartment tower located at 11503 100 Ave NW, in Edmonton, Alberta, Canada. The building was built in 1980, and the fire alarm system was upgraded in 2018.
This page will also cover the disconnected voice communication system.
System Specifications (2018-present)
FACP
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the parkade electrical room. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Annunciators
There is a Notifier LCD-160 annunciator paired with three Notifier ACM-24AT annunciators in the main lobby.
Booster Panels
There are numerous Notifier ACPS-610 addressable booster power supplies on the system.
Notification Appliances
All notification appliances are System Sensor "L-Series" P2RLA-E horn/strobes (red, wall-mount, English lettering, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout all common areas.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
There is a Notifier FSP-951A addressable photoelectric smoke detector by the parkade elevator lobby as a deficiency replacement.
All detectors are mounted on System Sensor B210LPA bases.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on all SLCs.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.
System Specifications (EVAC System)
The voice communication system in this building was utilized for paging and communication during emergencies; it was not an automated portion of the life safety system. Prior to the Notifier system being installed, this system likely utilized bells as notification appliances.
FACP
There is an Edwards 6700 conventional fire alarm panel installed in the main lobby. This panel also originally controlled the building's fire alarm system.
Notification Appliances
There are Soundolier UT720-8 remote speakers (white) on each floor.
There are Edwards 6703-70 high-output horn speakers throughout the parkade.
Firefighter's Telephones
There are Edwards 6702-0211 firefighter's telephones on each floor.