Lincoln Park Centre

From FireAlarmPedia
System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2023
Year Opened: 2008

Lincoln Park Centre is a medical and professional office building located at 5 Richard Way SW, Calgary, AB. The building was completed in 2008 and the fire alarm system is mostly original, with a third floor upgrade taking place in 2023.

System Specifications (2008-present)

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Booster Panels

There are two Notifier FCPS-24S8C 8-amp booster power supplies on the system. One is located above the ceiling in the north hallway, and the other is in the third floor tenant electrical room.

Notification Appliances

Most notification appliances on the first two floors are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
The third floor has System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, set to 15cd/electromechanical), as well as System Sensor PC2RLA horn/strobes (red, wall-mount, set to 15cd/electromechanical); the former can also be found as deficiency replacements.

Initiating Devices

Pull Stations

All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors in the stairwells and elevator lobbies.
The electrical closets have Notifier FST-851A addressable 135°F fixed-temperature heat detectors.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the elevator shafts.
The main electrical room has a Notifier FST-851HA addressable 190°F fixed-temperature heat detector.
All above detectors are mounted on Notifier B710LPA bases.
The air handling units have Notifier FSD-751PLA addressable photoelectric duct smoke detectors.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.