System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2024 Year Opened: 1986 |
Lucky Supermarket is a chain of grocery stores specializing in international products. This particular store is located at 2950 Calgary Trail NW, in Edmonton, Alberta, Canada. The building was built in 1986 as Gateway Cinemas, was converted into F2 Furnishings in 2011, and was extensively renovated in 2024 to become Lucky Supermarket. The fire alarm system was upgraded in 2011 and 2024; this page will cover the systems from both upgrades.
System Specifications (2024-present)
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances
All indoor notification appliances are System Sensor "L-Series" P2WLED-B horn/strobes (white, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor "SpectrAlert Advance" P2RKA weatherproof horn/strobe (red, wall-mount) outside the main entrance.
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-951A addressable photoelectric smoke detectors at the top of each stairwell, mounted on System Sensor B300A-6 bases.
There are System Sensor DNRA duct smoke detector housings with Notifier FSP-951A addressable photoelectric heads on all air handling units.
Modules
There are Notifier FMM-1A addressable monitor modules supervising all kitchen suppression systems, and the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.
EOLs
There are Notifier EOL-CR end of line resistor plates on all kitchen suppression, sprinkler and signal circuits.
Former System Specifications (2011-2024)
Former System Specifications |
---|
FACP: Simplex 4008 FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: N/A Date of last known Upgrade: N/A Year Installed: 2011 Year Decommissioned: 2024 |
FACP
The building was protected by a Simplex 4008 addressable fire alarm system. The panel was located in the main entrance vestibule. The system ran Simplex's IDNet addressable protocol, and the system coding was temporal.
Notification Appliances
All notification appliances were Wheelock MT-12/24R remote horns (red, wall-mount, set to horn).
Initiating Devices
Pull Stations
All pull stations were Simplex 4099-9001 addressable single-action pull stations.
Automatic Detection Devices
There were Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors at the top of each stairwell, mounted on Simplex 4098-9792 bases.
There were Simplex 4098-9755 duct smoke detector housings with Simplex 4098-9714 addressable photoelectric heads on all air handling units.
Modules
There were Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There were Simplex 4090-9002 addressable relay modules serving various purposes.
EOLs
There were Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.