More actions
System Specifications |
---|
FACP: Simplex 4100ES FACP Location: Multiple System Type: Two-Stage Networked Addressable System Line Voltage: 120VAC NAC Voltage: 70VRMS (audible) 24VDC (visual) System Coding: Unknown Strobes Synchronized: Yes, SmartSync Date of last known Upgrade: 2016 Year Opened: 1978 |
MNP Tower is an office building located at 10235 101 St NW, Edmonton, Alberta. The building was completed in 1978, and the fire alarm system was fully upgraded in 2016.
System Specifications (2016-present)
FACP
The building is protected by a Simplex 4120 networked fire alarm system. All nodes are Simplex 4100ES addressable panels. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice-evacuation. The system is configured for two-stage operation. The tones and/or messages are unknown.
Booster Panels
There are multiple Simplex 4009 booster power supplies on the system.
Notification Appliances
All notification appliances are Simplex “TrueAlert” 4906-9157 speaker/strobes (white, ceiling-mount, set to 30cd).
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004CA addressable two-stage pull stations.
Automatic Detection Devices
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors in some areas.
The electrical rooms and crawlspaces have Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors.
All detectors are mounted on Simplex 4098-9714 bases.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising the kitchen suppression system and sprinkler system’s tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 isolator modules on the SLCs.
EOLs