FACP: Mircom FX-2000 FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Mircom Date of last known Upgrade: 2025 Year Opened: 2012 |
Merecroft Gardens is an apartment building owned by Broadstreet Properties. This page will cover building D, located at 6149 Stanton Dr SW, Edmonton, AB. It was built in 2013, and the fire alarm system is mostly original, with parts replaced as deficiencies occur.
System Specifications (2012-present)
FACP
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.
Notification Appliances
All common area notification appliances are Mircom "Select-a-Horn/Strobe" horn/strobes (red, wall-mount, set to 15cd/electromechanical).
Each bedroom has a Mircom MH-S25WA silenceable mini-horn (white).
Initiating Devices
Pull Stations
All pull stations are Mircom MS-401AD addressable single-action pull stations.
Automatic Detection Devices
There are Mircom MIX-2251BA addressable photoelectric smoke detectors throughout the building.
There is a Mircom MIX-2351APA addressable photoelectric smoke detector on the 2nd floor as a deficiency replacement.
There is a Mircom MIX-5251HAPA addressable 190°F fixed-temperature heat detector in the boiler room.
All detectors are mounted on System Sensor B210LPA bases.
There is a System Sensor DNRA duct smoke detector housing with a Mircom MIX-2251BA addressable photoelectric head on the make-up air unit.
Modules
There are Mircom MIX-M500MA addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Mircom MIX-M500RA addressable relay modules serving various purposes.
There are System Sensor M500XA isolator modules on the SLC.
There are Mircom SDM-240 sync modules synchronizing all horn/strobes.
EOLs
There are Mircom MP-300 end-of-line resistor plates on all sprinkler and signal circuits.