| System Specifications |
|---|
| FACP: Edwards EST3X FACP Location: Main Electrical Room System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (Alert) Temporal (Alarm) Strobes Synchronized: Yes, Genesis Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2013 |
Million Air is a company providing private aircraft services. This page will cover Phase II of the Calgary branch, located at 235 Aero Way NE, in Calgary, Alberta, Canada. The building was built in 2013, and the fire alarm system is original.
System Specifications
FACP
The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the main electrical room. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. The alert signal is 20BPM, and the alarm signal is temporal.
This system is also used for foam suppression.
Booster Panels
There is an Edwards BPS6AC 6-amp booster power supply inside the main FACP.
Notification Appliances
All indoor notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd), equipped with Edwards "Genesis SignalMaster" G1M modules.
For outdoor notification, there is a System Sensor "SpectrAlert Advance" SRKA weatherproof remote strobe (red, wall-mount) outside the main electrical room.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices
There are EST SIGA2-PS addressable photoelectric smoke detectors at the top of each stairwell and in the main electrical room, mounted on EST SIGA-SB bases.
There are Spectrex SP-4040-1 flame detectors in the hangar.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the flame detectors, and the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on the SLC.
There is an EST SIGA-REL releasing module inside the FACP.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all flame detector, sprinkler and signal circuits.