More actions
System Specifications |
---|
FACP: Notifier NFS2-3030C FACP Location: Main Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Year Opened: 2022 |
PEXSISEN Elementary School is a public elementary school located at 3100 Constellation Avenue, in Victoria, British Columbia, Canada. The school opened in 2022, and the fire alarm system is original. This system is networked to Constellation Ave. Schools Central Plant and Centre Mountain Lellum Middle School.
System Specifications (2022-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the main electrical room. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Annunciators[edit | edit source]
There is a Notifier LCD2-80 annunciator and a custom graphic annunciator in the main entrance vestibule.
Boosters[edit | edit source]
There is a Notifier PS10C booster power supply in the main electrical room.
Notification Appliances[edit | edit source]
Most notification appliances are System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, bilingual lettering, set to 15cd).
Some classrooms and communication rooms have System Sensor HRLA remote horns (red, wall-mount).
For outdoor notification, there is a System Sensor “SpectrAlert Advance” SRKA-B weatherproof remote strobe (red, wall-mount, blue lens) outside the main entrance.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier N-MPS-SA addressable single-action pull stations. Most stations are equipped with Notifier MPS-LP dual-action conversion kits.
Automatic Detection Devices[edit | edit source]
There are Notifier FSP-951A addressable photoelectric smoke detectors throughout the building, and there are Notifier FST-951A addressable fixed-temperature heat detectors in all storage and electrical rooms. All detectors are mounted on System Sensor B300A-6 bases.
There are System Sensor D1420A conventional photoelectric duct smoke detectors on all air handling units, wired to Notifier FZM-1A addressable monitor modules.
The atriums have Notifier FS-OSI-RIA addressable beam detectors, with System Sensor RTS151KEY-A test switches wired to them.
Modules[edit | edit source]
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
EOLs[edit | edit source]
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.